ultrafilter inc. · · · ·
Refrigeration Compressed Air Dryer BOREAS
Technical data
BOREAS SD 1950 A - SD 8750 A (60 Hz-Version)
SD1950
1
R 134 a
1200
6100
3.78
2.76
4"
3/4"
47.24
74.8
49.41
948
SD2250
1
R 134 a
1400
6100
4.44
2.76
4"
3/4"
47.24
74.8
49.41
992
SD2750
1
R 134 a
1600
6100
4.68
3.6
4"
3/4"
47.24
74.8
49.41
1014
SD3500
1
R 134 a
2000
5800
6.84
2.46
6"
3/4"
47.24
74.8
49.41
1322
SD4000
1
R 134 a
2400
5800
7.56
3.2
6"
3/4"
47.24
74.8
49.41
1345
SD5000
1
R 134 a
3000
5800
9.84
3.6
6"
1"
47.24
74.8
49.41
1422
SD7000
2
R 134 a
4000
12000
14.64
3.6
8"
1"
87.6
74.8
49.41
2227
Typ
cfm
cfm
kW
V/60Hz
psi
150 lbs
NPT
inch
inch
inch
lb
3 / 460 V
Designation
1 Housing version
2 Refrigerant
3 Volume flow
4 Cooling air required
5 Power consumption
6 Mains voltage
7 Pressure drop
8 Air connections (Ansi)
9 Condensate drain
10 Main
Width
W
dimensions
Height H
Depth D
11 Weight
SD8750
2
R 134 a
5000
11500
17.4
3.8
8"
1"
87.6
74.8
49.41
2602
Low pressure drop due to large flow channels
Pollution repellent aluminium plates
Cyclone separator
Microprocessor controlled zero loss drain
SAB-Processor SP 3
Constant pressure dew point by means of thermostatic expan-
sion valve and power control
Electronic control of major functions by state-of-the-art
technology
Space-saving installation by front operating elements, conden-
sate drain and cooling air inlet
Application of solid, fully hermetic refrigerant compressors
Galvanised, stove-enamel sheet steel case in modern
industrial design
No TÜV-approval required
The electrical installation is carried out in accordance with
EN 60204, all technical data comply with CAGI ADF 100.
Safety regulations are in accordance with the regulations for
prevention of accidents UVV VBG 20.
Low running cost
Eco-friendly refrigerant R 134a
C UL approval
Technical data comply with CAGI ADF 100
Modular construction
Optional: Energy saving device (Standby mode for zero load
operation)
W
D
H
s
Cooling air
outlet
Cooling air
inlet
Compressed
air inlet
Compressed
air outlet
BOREAS DSM significant advantages:
- Fully hermetic and maintenance-free refrigerant compressor
- Air cooled condenser
- Aluminium air/air and refrigerant/air-heat exchanger
- Maintenance-free separator
- Electronically level-controlled condensate drain, ultramat
- Refrigerant capacity control
- Thermostatic expansion valve
- Insulation free of CFC
- Galvanised, stove-enamel sheet steel case
- Dry contact for generel alarm
- Dry contact for dew point alarm
- Working hour meter
Item 3: Volume flow referred to suction status of the air compressor +68°F, 14.5 psi g, compressed air inlet temperature +100°F, operating pres-
sure 100 psi g, pressure dew point +35°F - at dryer outlet Item 5: Power consumption at an ambient temperature of +100°F
Standard version air cooled · Permissible ambient temperatures: min. +36°F, max. +122° F · Max. permissible operating pressure: 232 psi g,
higher pressures on request · Protection class: IP 54 · Sound pressure level: dB(A) < 80 · Technical data in according to CAGI ADF 100.
Specifications are subject to change without notice.
Standard equipment
Please contact
Filter Products at 804-231-4646 to place an order or for more information about this product.